Wire gauge: converting AWG to mm², formula and table

Why smaller AWG numbers are thicker, the exact diameter formula, an AWG to mm² table, and how metric 1.5 and 2.5 mm² cables map onto AWG sizes.

📚 Units and notation: why there are so many · 41/45· ⏱ About 3min read ·Information updated 2026-11-03
📋 Key facts5
Diameter
d (mm) = 0.127 × 92^((36 − n) ÷ 39)
Cross-section
A (mm²) = π ÷ 4 × d²
AWG 14
About 1.628 mm, 2.08 mm²
AWG 12
About 2.053 mm, 3.31 mm²
Rule of thumb
Every 3 gauges ≈ 2× area; every 6 gauges ≈ 2× diameter

Two ways to size a wire

Korea and Europe size conductors by cross-sectional area in mm², using standard values from IEC 60228 such as 1.5, 2.5, 4 and 6 mm². The US and Canada use American Wire Gauge (AWG) numbers. Imported electronics, speaker wire, car wiring and charging cables often carry AWG labels, so converting between the two comes up often.

Why smaller numbers are thicker

AWG numbers come from how many times wire was drawn through dies to make it thinner. More drawing means thinner wire, so a higher number is a finer wire: AWG 24 is thin signal wire, AWG 10 heavy power wire. Sizes thicker than 0 are written 1/0, 2/0 and so on up to 4/0.

The exact formula

AWG fixes gauge 36 at 0.005 inch (0.127 mm) and 4/0 at 0.46 inch, with 39 equal-ratio steps between them. So the diameter of gauge n is d = 0.127 mm × 92^((36 − n) ÷ 39), where 92 = 0.46 ÷ 0.005. Area is π ÷ 4 × d². For AWG 14 that gives about 1.628 mm and 2.08 mm².

AWG to mm² table

Values from the formula above, rounded.

  • AWG 24: 0.511 mm, 0.205 mm²
  • AWG 22: 0.644 mm, 0.326 mm²
  • AWG 20: 0.812 mm, 0.518 mm²
  • AWG 18: 1.024 mm, 0.823 mm²
  • AWG 16: 1.291 mm, 1.31 mm²
  • AWG 14: 1.628 mm, 2.08 mm²
  • AWG 12: 2.053 mm, 3.31 mm²
  • AWG 10: 2.588 mm, 5.26 mm²

Easy rules

Because 39 steps span a factor of 92, every 3 gauges smaller multiplies area by about 2.005 and every 6 gauges doubles the diameter. Ten gauges multiply area by about 10.2, so AWG 10 has roughly ten times the area of AWG 20. Resistance is inversely proportional to area, so for the same length a wire three gauges thicker has about half the resistance.

Metric sizes in AWG

Running the formula backwards, 1.5 mm² is about AWG 15.4, 2.5 mm² about AWG 13.2, 4 mm² about AWG 11.2 and 6 mm² about AWG 9.4. The two systems do not line up exactly, so when substituting choose the size with equal or larger area. In place of 2.5 mm², use AWG 12 (3.31 mm²), not AWG 14 (2.08 mm²).

Check current ratings separately

How much current a wire can safely carry depends on insulation, installation method, ambient temperature and grouping, not just size. Use the applicable wiring code (in Korea, the KEC) and the manufacturer's tables; do not guess ampacity from a size conversion. Household wiring work belongs with a licensed electrical contractor.

Summary

AWG is a number; mm² is the actual area.

  • d = 0.127 × 92^((36 − n) ÷ 39) mm
  • Smaller number, thicker wire
  • Every 3 gauges ≈ double the area
  • 2.5 mm² ≈ AWG 13.2; substitute AWG 12
  • Check ampacity in code and maker tables